Fluke 975 AirMeter Indoor Air Quality Meter

$0.00

The Fluke 975 offers an unparalleled feature set for HVAC and facilities technicians, helping them work more quickly and accurately, with the ease of use and durability customers expect from a Fluke meter.

Simultaneously measures, logs, and displays temperature, humidity, CO2, and CO on a bright, backlit LCD display

    Fluke 975 Datasheet

    Fluke 975 User Manual

    HVAC-IAQ Selection Guide

If you would like more information regarding this product, simply email us here.

  • Enter your query
  • Drop files here or
    Accepted file types: jpg, gif, png, pdf, Max. file size: 1 MB, Max. files: 4.
    • This field is for validation purposes and should be left unchanged.

    Fluke 975 AirMeter Indoor Air Quality Meter- One Tool. Get More Done.

    The Fluke 975 AirMeter test tool raises indoor air monitoring to the next level by combining five powerful tools in one, rugged and easy-to-use handheld device. Use the Fluke 975 to optimize HVAC ventilation settings for ASHRAE 62 recommendations, actively monitor conditions that promote a productive environment, and quickly and accurately address occupant comfort complaints the first time.

    The Fluke 975 measures:

    • Temperature
    • Velocity
    • Humidity
    • CO2
    • CO

    Use the Fluke 975 AirMeter test tool to:

    • Respond to comfort-related calls from occupants.
    • Verify the operation of building HVAC control systems.
    • Determine whether adequate ventilation exists.
    • Monitor air flow and velocity.
    • Test for dangerous carbon monoxide leaks.
    • Perform duct traversals.
    • Optimize HVAC systems to manage energy costs

    Simultaneously measures, logs, and displays temperature, humidity, CO2, and CO on a bright, backlit LCD display

    975 AirMeter Features:

    • One-touch air flow and velocity with available probe*
    • Wet bulb and dew point temperature
    • % of outside air calculation
    • CO2 and CO field calibration feature
    • Self-test function at startup
    • Auto-backlight
    • Automatically compensates for barometric pressure changes
    • Min/Max/Average on all measured and calculated readings
    • Multi-language user interface
    • Metric or standard units
    • Audible and visual threshold alarms
    • Extensive discrete or continuous data logging capacity, downloadable to PC via USB interface
    • Keypad lock for security
    • Included FlukeView Forms® software
    • *Included with Fluke 975V, optional with Fluke 975

    Fluke 975 AirMeter Specifications:

    Measured Specifications
    Temperature Range -20°C to 50°C (-5°F to 122°F)
    Display resolution 0.1°C (0.1°F)
    Accuracy ±0.9°C / ±1.62°F from 40°C to 60°C
    ±0.5°C / ±1.00°F from 5°C to 40°C
    ±1.1°C / ±1.98°F from -20°C to 5°C
    Relative humidity Range 10% to 90% RH, non-condensing
    Display resolution 1%
    Accuracy ±2% RH (10% RH to 90% RH)
    Air velocity Range 50.0 fpm to 3000 fpm
    0.25 m/sec to 15 m/sec
    Display resolution 1 fpm (0.005 m/sec)
    Accuracy ±4% or 4 fpm1
    ±4% or 0.02 m/sec1 whichever is greater
    1. Accuracy specification only valid for velocity readings above 50 fpm.
    C0 Range 0 to 500 ppm
    Display resolution 1 ppm
    Accuracy ±5% or ±3 ppm, whichever is greater, @ 20°C and
    50% RH
    C02 Range 0 to 5000 ppm
    Display resolution 1 ppm
    Accuracy Warm up time 1 min (5 minutes for full specification) 2.75% + 75 ppm
    Calculated Specifications
    Dew point temperature Range -44°C to 50°C, (-47°F to 122°F)
    Display resolution 0.1°C (0.1°F)
    Accuracy ±1°C when temp: -20°C to 50°C RH: 40% to 90%
    ±2°C when temp: -20°C to 50°C RH: 20% to 40%
    ±4°C when RH: 10% to 20%
    Wet bulb temperature Range -16°C to 50°C, (3°F to 122°F)
    Display resolution 0.1°C, (0.1°F)
    Accuracy ±1.2°C when RH: 20% to 90% temp: -20°C to 60°C
    ±2.1°C when RH: 10% to 20%
    Volume flow rate (in a duct) Range 0 to 3,965 M3/m, (0 to 140,000 cfm)
    Display resolution 0.001 M3/min, (1 cfm)
    Accuracy N/A: The volume flow calculation will be a simple average of the data points times the duct area
    % outside air (based on temperature) Range 0 to 100%
    Display resolution 0.1
    % outside air (based on CO2) Range 0 to 100%
    Display resolution 0.1% N/A
    General Specifications
    Operating and storage temperature -20°C to 50°C (-4°F to 122°F)
    Humidity 10% to 90% (non-condensing)
    Altitude Up to 2000 m (6562 ft)
    Shock and vibration MIL-PRF-28800F: Class 2
    Multi-language interface English, French, Spanish, Portuguese and German
    Battery Rechargeable Li-Ion (primary), three-AA (backup)
    Data logging 25,000 records (continuous), 99 records (discrete)
    Warranty Two-years