The REED C-380 is a Refrigerant Gas Leak Detector was especially designed for detecting even the smallest leaks of refrigerant gases in domestic and commercial refrigeration systems, automotive, air conditioning and quality control testing environments.
The REED C-380 comes with flexible 390mm gooseneck probe and is powered by last generation microprocessor control with advanced digital signal processing.
Thanks to its instantaneous response time, Reed C-380 Refrigerant Gas Leak Detector assures excellent performance and accuracy even in hard to reach areas. This meter features also visual and audible alarm and multi-colour visual display.
REED C-380 Specifications
- Gases Sensed: CFCs: R11, R12, R13; HCFCs: R22, R502,
R500; HFCs: R134a, R123, R125, R23, R404A,
R407C, R410A & other halogen based compounds - Sensitivity: R22, 134a: Hi 6g/year, L: 30g/year
R404A, 407C, 410A: Hi 8g/year, L: 40g/year - Alarm Settings: Buzzer, Tricolour LED bar indicator
- Sensor: Advanced ionization detection
- Response Time: Less than 1 second
- Warm-up Time: 10 seconds
- Probe: 390mm (15”) flexible stainless probe
- Ambient Conditions: 32 to 104°F (0 to 40°C), 0 to 80% RH
- Power Supply: Four AA alkaline battery, Low battery indication
- Auto Power Off: 10 minutes
- Battery Life: Approx. 40 hours
- Dimensions: 17.3 x 6.6 x 5.6 cm
- Weight: 500 g
Includes:
- Reference leak source,
- carrying case and batteries
How to use Refrigerant Gas Leak Detector (C-380)
Power-Up & Reset the instrument
Press ON/OFF once to turn on the refrigerant leak detector. The sensor will heat up for 1.5 minutes and you have to wait for proper functionality. Press the ON/OFF again to reset the ambient concentration for the unit. After this time reset the ambient concentration for the unit by pressing the ON/OFF button again.
Sensitivity Adjustment
When the unit is switched ON it is set to high sensitivity by default. To change the level of sensitivity to LOW, press the “Lo Sensitivity” button. To switch the unit back to high sensitivity, press the “Hi Sensitivity” button
Automatic Ambient Setup
This “ambient concentration reset function” sets the unit sensors to ignore the ambient concentrations of refrigerant present. When turned ON the unit’s sensor, the instrument using itsAutomatic Ambient Setupto set itself to ignore the level of refrigerant present at the tip. Only a level or concentration great than this will cause the unit to alarm.
During the gas leak operations, resetting the instrument using the Ambient Reset Feature programs the circuit to ignore the level of refrigerant present at the tip of the sensor.
Measuring gas leak with C-380 instrument
Find out the suspected leak source and position the tip of the sensor probe within 1/4 inch (6 mm) of this. Slowly move the sensor probe past each possible leakage point.
When the unit detects a leak source an audible tone will sound and visual indicators will light on the LED leak indicator display, appearing from left to right. The visual indicator will be green to orange to red (red being the highest concentration, green the lowest). When the unit signals a leakage, pull the probe away from the leak for a moment and then bring it back slowly to pinpoint the location. If the refrigerant leak is large setting the sensitivity switch to LOW (see sensitivity adjustment) will make it easier to find the exact site of the leak. Return the sensitivity switch to HIGH before searching for any additional leaks. When you’ve finished testing for leaks turn the unit OFF and store it in a cool, dry, clean place to protect the sensor and unit from any possible damage.